Power Factor Correction Calculator

Reviewed September 2026

Size a capacitor bank from present and target power factor, then see the effect on kVA, current and capacitance.

01 // Electrical load

02 // Capacitor-bank requirement

—
Reactive power before—
Reactive power after—
Apparent power before → after—
Line current before → after—
Capacitance per phase—

Worked example

A 100 kW three-phase induction-motor load on a 400 V, 50 Hz supply, measured at 0.75 power factor, corrected to 0.95.

Step 1 — reactive power now. φ1 = arccos 0.75 = 41.4°, so Q1 = P tan φ1 = 100 × 0.882 = 88.2 kvar.

Step 2 — reactive power wanted. φ2 = arccos 0.95 = 18.2°, so Q2 = 100 × 0.329 = 32.9 kvar.

Step 3 — bank size. Qc = Q1 − Q2 = 55.3 kvar. In practice you would specify the next standard step up, typically a 60 kvar bank in 5 or 10 kvar stages.

Step 4 — what it buys. Apparent power falls from 100/0.75 = 133.3 kVA to 100/0.95 = 105.3 kVA, and line current from 192 A to 152 A — a 21% reduction in both. That current reduction is the part that matters for cable and transformer loading.

Step 5 — capacitance. For a delta-connected bank at 400 V, C = Qc/(3ωVLL2) = 367 µF per phase. The same duty in star needs 1101 µF per phase, because each capacitor sees only 231 V. Delta is the usual choice at low voltage for exactly this reason: three times the voltage means a third of the capacitance and a smaller, cheaper unit.

Two consequences follow from step 4 that are easy to miss. Losses in the supply cable fall with the square of current, so a 21% current reduction cuts I²R loss by about 38%. And the released 28 kVA of transformer capacity is often worth more than the energy saving — it can defer a transformer upgrade entirely.

Assumptions and where this stops being valid

The calculation is a single-operating-point sizing check. Five things it does not model.

1. Sinusoidal, balanced supply. Qc = P(tan φ1 − tan φ2) assumes a clean fundamental waveform. With significant harmonic distortion the displacement power factor this calculates is no longer the true power factor, and correcting to the displayed target will not give the expected result.

2. Harmonic resonance is not checked. This is the one that damages equipment. A capacitor bank forms a parallel resonant circuit with the supply transformer inductance. The approximate resonant harmonic order is hr ≈ √(Ssc/Qc), where Ssc is the fault level at the busbar. For a 1000 kVA transformer at 6% impedance, Ssc ≈ 16.7 MVA, and a 55 kvar bank gives hr ≈ 17 — comfortably clear. The same bank on a 315 kVA transformer gives hr ≈ 9.5, close to the 9th and 11th harmonics of a six-pulse drive. That is a resonance waiting to happen, and it calls for detuned reactors.

3. Fixed correction assumes a fixed load. Sizing at full load and leaving the bank permanently connected produces leading power factor at light load, which some utility tariffs penalise as heavily as lagging. Variable loads want automatic stepped banks with a power-factor controller.

4. Motor terminal correction has a limit. Capacitors connected directly at motor terminals must stay below the motor's no-load magnetising kvar, or the motor can self-excite when the supply is interrupted while it is still spinning, generating damaging overvoltage.

5. Inrush is not sized. Switching a capacitor step draws a high-frequency inrush current, and back-to-back switching of parallel steps is worse. Contactors need capacitor-duty rating or damping reactors.

Standards and what to do next

Capacitor units: IEC 60831-1 and -2 for low-voltage self-healing units up to 1 kV; IEC 60871-1 for shunt capacitors above 1 kV. Both set tolerance, loss, discharge and endurance requirements. Capacitors are rated for 1.1 × rated RMS voltage continuously and 1.3 × rated RMS current, the latter allowing for harmonic content.

Harmonic assessment: IEEE 519 for voltage and current distortion limits at the point of common coupling. IEC 61000-2-4 for compatibility levels inside an industrial installation.

Before ordering a bank: measure over a full production cycle rather than at one instant — a power quality logger over a week will show the load variation that decides fixed versus automatic. Record the harmonic spectrum at the same time. Check the transformer fault level and run the resonance estimate above. If hr lands within two orders of a harmonic your drives actually produce, specify detuned reactors (commonly tuned to 189 Hz or 134 Hz on a 50 Hz system) rather than plain capacitors.

Background & method

The fundamental relation is Qc = P(tan φ1 − tan φ2). The calculator then derives current and capacitor values for the selected electrical configuration. Harmonic and switching design remains a separate engineering task.