Skip to content

Drawing No. EH–TH–042 // Thermal Engineering & HVAC

Ventilation, Airflow & ACH Calculator

Reviewed August 2026

Calculate room volume, airflow, air changes per hour, air-change time, occupancy ventilation, and ideal contaminant-removal time.

Scope: A preliminary well-mixed-room calculator. It does not model duct pressure loss, fan selection, short-circuiting, stratification, heat loads, or code-required design rates.

What this calculator does

Enter room dimensions and either airflow or target air changes per hour. The tool calculates the corresponding ventilation rate and estimates ideal contaminant decay. An optional occupancy rate provides a simple comparison against airflow per person.

How to use this ventilation calculator

1Choose what you know

Select “calculate airflow” when you have a target ACH, or “calculate ACH” when you know the fan or measured airflow.

2Measure the room

Enter internal length, width and average ceiling height. The tool calculates the air volume.

3Add occupants if useful

Enter people and an outdoor-air rate only as a comparison. Local rules may use different methods.

4Choose a removal target

Use the decay section to estimate ideal airing time after a one-time release with no continuing source.

Important: fan label airflow is not always delivered airflow. Duct resistance, filters, grilles and poor air paths can reduce the real value.

Inputs

Quick examples

Room geometry
Ventilation basis
Ideal contaminant decay
Use the same units for all three values. The target must be above the incoming/background concentration.

Results

Enter valid room and ventilation values.
Room volume
Required / actual airflow
Air changes per hour
Minutes per air change
Airflow per person
Occupancy-based airflow
Ideal decay time
Air changes for decay
Occupancy comparison: Enter occupants to compare the calculated airflow with a chosen per-person value.

Worked example: 30 m³ bedroom at 1 ACH

Required airflow

1 ACH × 30 m³ = 30 m³/h of outdoor air.

Air-change time

One theoretical air change takes 60 minutes at 1 ACH.

Ideal 90% removal

With zero background and no continuing source, 90% removal requires about 2.30 air changes, or roughly 138 minutes.

Background

Engineering basis, interpretation, guidance and limitations for room ventilation calculations.

Frequently Asked Questions

Practical questions about ACH, airflow, occupancy and ideal contaminant decay.