Building Energy & Services

Reviewed October 2026

Estimate building heat loss, HVAC and ventilation needs, lighting, hot water, humidity risk and envelope performance for preliminary building-services work.

13 calculators & tools9 governing standards referencedBuilding as the system boundary

Building-services engineering asks a different question from plant engineering. The plant engineer sizes a coil, a tower or a heat exchanger against a known duty. The building-services engineer has to establish what that duty is — from fabric, weather, occupancy and ventilation — before any equipment can be selected at all. Every tool on this page sits upstream of equipment selection, with the building or the room as the system boundary.

The sequence below is the order the calculations actually have to run in, because each step consumes the output of the one before it. Getting the order wrong is the most common reason a preliminary design has to be redone: an emitter schedule built on a screening heat load, or a boiler chosen before the hot-water peak is known, cannot be corrected by refining the later steps.

Equipment-side and thermodynamic-process tools — coils, psychrometrics, cooling towers, condensers, chillers, steam and refrigeration cycles — live in Thermal Engineering & HVAC. Homeowner-facing versions of several of these questions live in Household Engineering Tools.

The order the work has to run in

From weather file to equipment schedule

Each step below consumes the result of the previous one. Steps 1–3 establish the load; steps 4–6 turn that load into hardware; steps 7–9 check that the design does not fail in summer, at part load, or on the inside face of the envelope.

  1. Fix the design conditions

    External design temperature θe comes from the national annex to EN 12831-1, not from an annual minimum — it is a statistical value tied to a return period. Internal design temperatures come from EN 16798-1 categories or ASHRAE 55. Both numbers propagate into every later step, so a 2 K error here is a 2 K error everywhere.

    No calculator — take these from the applicable annex before you start.

  2. Establish fabric U-values

    EN ISO 6946 sums layer resistances between fixed surface resistances: Rsi = 0.13 m²K/W for horizontal heat flow through a wall, Rse = 0.04 m²K/W outside. The layer arithmetic is easy; the part people omit is the thermal-bridge correction ΔU, which on a repeating-bridge wall is routinely 0.02–0.15 W/m²K — a meaningful fraction of a modern wall's total.

    Tools: Insulation / U-value / R-value · Wall heat transfer

  3. Calculate the design heat load

    EN 12831-1 splits the room load into transmission, ventilation and — where intermittent heating is used — a reheat term: ΦHL = ΦT + ΦV + ΦRH Do this room by room if emitters are to be sized from it. A whole-building figure is adequate for generator capacity and useless for emitter selection.

    Tools: Building heat loss · HVAC BTU load

  4. Size the emitters — and correct the catalogue rating

    Radiator outputs are published to EN 442-2 at a reference excess temperature of 50 K. Real systems almost never run there. Correct with

    Q = Q50 × (ΔT / 50)n, n ≈ 1.3 for panel radiators

    At 55/45 °C flow/return into a 20 °C room the excess temperature is 30 K, so the factor is (30/50)1.3 = 0.51. A radiator catalogued at 1 kW delivers about 515 W. This single exponent is why low-temperature retrofits need roughly double the installed radiator surface, and why heat-pump conversions fail when the existing emitters are simply reused.

    Tool: Radiator sizing

  5. Set flows and balance the circuit

    Flow follows from the emitter duty and the design temperature drop, ṁ = Φ / (cp · ΔT) which for 1 kW at ΔT = 10 K and cp = 4.18 kJ/kgK is 0.024 kg/s, about 86 kg/h. Balancing then converts that flow and the pressure available at each valve into a Kv setting, Kv = Q / √Δp with Q in m³/h and Δp in bar.

    Tool: Radiator balancing wizard

  6. Choose the generator — check which load actually governs

    For a house, space heating and domestic hot water are usually not the governing load at the same time, and in a combi installation DHW almost always wins. Ten litres per minute at a 35 K rise is 0.167 kg/s × 4.18 kJ/kgK × 35 K ≈ 24 kW which is why 24 kW combis are ubiquitous in dwellings whose design heat loss is 5–8 kW. Size the heat output to the heating load and the instantaneous output to the hot-water draw, then take the larger — or decouple the two with storage.

    Tools: Boiler size · Water heater / hot-water sizing

  7. Set the ventilation rate

    ASHRAE 62.1 builds the breathing-zone rate from a per-person and a per-area term, Vbz = RpPz + RaAz; EN 16798-1 does the same with category-dependent values. CO₂ is the practical check rather than the design basis: a sedentary adult generates about 0.0045 L/s of CO₂, so holding 1000 ppm against a 400 ppm outdoor baseline needs 0.0045 / 0.0006 ≈ 7.5 L/s per person at steady state.

    Tool: Ventilation, airflow & ACH

  8. Check summer overheating before glazing is fixed

    Overheating is a geometry and glazing decision, not a cooling decision, and it is settled long before plant is specified. Solar gain through unshaded south or west glazing can exceed the entire winter design heat loss of a well-insulated room. Assess against the EN 16798-1 adaptive criteria or CIBSE TM59 rather than a single peak temperature.

    Tool: Room overheating & solar shading

  9. Verify surface temperatures, not just air temperatures

    Mould grows at surface relative humidity around 80%, well before liquid condensation appears. EN ISO 13788 handles this with the temperature factor fRsi = (θsi − θe) / (θi − θe) compared against a critical value commonly taken as 0.75 for dwellings in national guidance. A wall that passes on U-value can still fail here at a reveal, a lintel or a balcony slab.

    Tools: Window condensation & mould risk · Dehumidifier sizing

Calculators & tools

13 pages

Boiler Size Calculator for Homes & BuildingsEstimate boiler capacity from floor area or a detailed building-envelope and ventilation heat-loss calculation, including combi hot-water demand.Calculator / tool→Building Heat Loss CalculatorTwo-mode building heat-loss calculator: a fast screening estimate and a detailed component method with wall, window, door, roof, floor and infiltration breakdown.Calculator / tool→Dehumidifier Sizing CalculatorSize a portable or whole-space dehumidifier using ENERGY STAR room guidance or a psychrometric moisture-load model.Calculator / tool→HVAC BTU Load CalculatorEstimate heating and cooling capacity in BTU/h, kW and tons with basic room sizing or an advanced envelope, ventilation, solar and internal-gain model.Calculator / tool→Insulation / U-Value / R-Value CalculatorBuild a layered wall, roof or floor visually and calculate U-value, SI/US R-value, heat loss, inside surface temperature, dew point and added insulation needed.Calculator / tool→Radiator Balancing WizardCalculate required flow rate and balancing valve Kv setting for up to 6 radiators from heat output, system temperature drop and available pressure at each valve.Calculator / tool→Radiator Sizing CalculatorSize a radiator from room heat loss and water temperatures. Estimate ΔT50 catalogue rating, correction factor and hydronic flow in SI or US units.Calculator / tool→Room Lighting Lux Layout & Reflectance CalculatorEstimate luminaire count and a regular room layout with the lumen method using room index, a manufacturer-provided utilization factor, maintenance factor and luminaire spacing-to-height…Calculator / tool→Room Overheating & Solar-Shading CalculatorEstimate room overheating from windows, weather and internal heat. Combine shading, smart ventilation, reduced gains and active cooling.Calculator / tool→Ventilation, Airflow & ACH CalculatorCalculate room airflow, CFM, m3/h, air changes per hour and ideal airing time. Compare ventilation with room volume, occupants and a removal target.Calculator / tool→Wall Heat Transfer CalculatorCalculate steady-state wall heat transfer, U-value, thermal resistance, heat flux, surface temperatures and layer-by-layer temperature drops. Supports SI and US customary units.Calculator / tool→Water Heater / Hot-Water Sizing CalculatorSize storage or tankless water heating from peak-hour demand, tank temperature, recovery power, temperature rise and simultaneous flow.Calculator / tool→Window Condensation & Mould-Risk CalculatorCheck whether a measured cold window, frame or wall will condense. Calculate dew point, surface humidity and practical moisture-control actions.Calculator / tool→

Reference

Which document governs which step

Preliminary tools are only defensible if you can say what they are approximating. This maps each step to the document a reviewer will expect, with the European and North American routes side by side.

StepEuropean routeNorth American routeWhat the standard fixes
Design conditionsEN 12831-1 + national annexASHRAE Handbook — Fundamentals, ch. 14θe return period, internal set points
Comfort criteriaEN 16798-1ASHRAE 55Operative-temperature bands by category
Fabric U-valueEN ISO 6946ASHRAE Handbook — Fundamentals, ch. 25–27Surface resistances, layer summation, ΔU
Thermal bridgesEN ISO 10211 / 14683ASHRAE 90.1 App. Aψ-values and default bridge catalogues
Design heat loadEN 12831-1ACCA Manual JTransmission, ventilation, reheat terms
Cooling loadEN ISO 52016-1ASHRAE RTS / Manual JDynamic gain treatment, thermal mass
Emitter outputEN 442-2Manufacturer I=B=R ratingsTest conditions and ΔT reference
Ventilation rateEN 16798-1ASHRAE 62.1 / 62.2Per-person and per-area airflow
Surface condensationEN ISO 13788ASHRAE 160fRsi criterion, moisture balance

Failure modes

Where preliminary building-services work goes wrong

These three account for most of the corrections made between a screening calculation and a design that survives review. None of them are arithmetic errors.

Selecting emitters from a screening heat load

A W/m² rule of thumb is a legitimate way to establish generator capacity to about ±20% — the honest spread runs from roughly 25–35 W/m² for a current-regulation dwelling to 90 W/m² and above for an uninsulated solid-wall building. It is not a legitimate way to size the radiator in a specific room, because the screening figure averages over orientation, exposure, glazing ratio and the number of external walls. The corner room with two external walls and a large window can carry two or three times the per-area load of an internal room on the same floor. Emitters need the room-by-room calculation.

Using the catalogue radiator output directly

The ΔT50 correction in step 4 is the most consequential single factor on this page and the one most often skipped. Taking a catalogue figure at face value on a 55/45 °C system under-sizes the emitter by about a factor of two. The symptom is a system that performs acceptably in mild weather and cannot reach set point on the coldest days — which is then misdiagnosed as a generator or control problem.

Sizing the heat generator before the hot-water peak is known

Space-heating load and DHW load scale with completely different things: one with fabric and weather, the other with the number and type of outlets. In dwellings the hot-water draw usually governs the instantaneous rating; in a building with storage and a reasonable draw-off profile it usually does not. The decision of which governs has to be made before the generator is chosen, not after, because it also determines whether storage is needed at all.

Scope

Where these tools stop

Everything on this page is a steady-state, single-zone screening calculation. That is a deliberate choice — it is the right level of effort for feasibility work, option comparison and sanity-checking someone else's output. It is the wrong level of effort for the following, and no amount of care with the inputs will change that:

Each individual page states its own assumptions and the point at which its method stops being valid. Read that section before using a result for anything that will be built.